GECA Leak Detector Panel

GECA Leak Detector Panel

Mains-powered domestic and light-commercial leak detector by GECA of Italy, with green LINE, yellow FAULT and red ALARM indications and a relay output for a solenoid safety valve.

Prices on request. Contact us for availability and quotations.

Description

A wall-mounted leak detector carrying the GECA maker's mark. A catalytic sensor draws room air and the unit raises an optical and acoustic alarm when the concentration in the room passes the alarm threshold. The front panel carries three indications: a green LINE lamp showing the unit is powered, a yellow FAULT lamp showing the sensor has failed, and a red ALARM lamp for an alarm.

The alarm relay is intended to drive a normally open solenoid safety valve on the monitored line, so that a leak both sounds the alarm and shuts the supply. The valve must be fitted on the pipework outside the room being monitored, because a valve inside the room gives no protection against a leak upstream of it.

GECA builds its detectors in two versions, one for a medium lighter than air and one for a medium heavier than air. They are not interchangeable, and the mounting height is opposite: the heavier-than-air version is mounted low, because the medium collects near the floor, while the lighter-than-air version is mounted high. State the medium when ordering, and state whether the unit is to be wired to a normally open or a normally closed valve.

Specifications

Panel Indications Green LINE (unit powered), yellow FAULT (media sensor damaged), red ALARM (media concentration above the alarm threshold)
Alarm Threshold GECA states its detectors are calibrated to alarm at 10 % of the LEL (lower explosive limit)
Service Life GECA states the alarm threshold will not exceed 15 % LEL during the first four years; after that period the detector must be taken out of service and replaced
Standard GECA declares its GAMMA 654-O / 656C domestic detectors to CEI UNI EN 50194-1:2009 (electrical apparatus for the detection of combustible media in domestic premises). The unit photographed is not identified to a model, so confirm the marking on the unit supplied.
Media Versions Separate the lighter-than-air medium (/M) and the medium named in its standard (/G) versions; not interchangeable. The medium named in its standard units are mounted low, the lighter-than-air medium units high — GECA specifies a maximum of 30 cm from the floor or ceiling respectively.