WIKA A-10 Pressure Sensor (General Industrial) – 4-20 mA, 0-10 V, 316L Stainless Steel, IP65–IP69K

WIKA

WIKA A-10 Pressure Transmitter – 4-20 mA / 0-10 V, 316L, IP65/IP67

Model A-10

WIKA model A-10 pressure transmitter for general industrial service. Gauge ranges 0…0.05 to 0…1,000 bar, 4…20 mA or DC voltage output, 316L wetted parts and IP65/IP67 protection. Used in machine building, hydraulics and pneumatics, pumps and compressors.

Prices on request. Contact us for availability and quotations.

Documents

Need a certificate we have not listed? Ask us and we will send it.

Description

The WIKA model A-10 is a piezoresistive pressure transmitter for general industrial pressure measurement. It is supplied in gauge, absolute and vacuum/compound versions, with gauge ranges from 0…0.05 bar to 0…1,000 bar [0…1 to 0…15,000 psi] and absolute ranges from 0…0.1 to 0…25 bar abs. Non-linearity is ≤ ±0.5 % of span, or ≤ ±0.25 % of span for ranges above 0.1 bar.

The measuring cell is welded into a stainless steel process connection. Wetted parts are stainless steel 316L below 10 bar, and 316L with PH grade steel at and above 10 bar, where the cell runs dry rather than oil-filled. Output is 4…20 mA two-wire, or a three-wire DC voltage signal (0…10 V, 0…5 V, 1…5 V, 0.5…4.5 V), or a ratiometric DC 0.5…4.5 V signal against a 5 V supply.

Typical duties are machine building, measurement and control, hydraulics and pneumatics, pumps and compressors, and shipbuilding. Service life is up to 100 million load cycles for measuring ranges above 0.1 bar.

When ordering, state the measuring range and pressure type, the output signal and supply voltage, the process connection and its seal, the electrical connection — which sets the ingress protection at IP65 or IP67 — and the required medium temperature range.

Specifications

Measuring Range (Gauge) 0…0.05 to 0…1,000 bar [0…1 to 0…15,000 psi]
Measuring Range (Absolute) 0…0.1 to 0…25 bar abs.
Accuracy Non-linearity ≤ ±0.5 % of span; ≤ ±0.25 % of span for ranges > 0.1 bar (BFSL per IEC 61298-2)
Output Signal 4…20 mA (2-wire); DC 0…10 V, 0…5 V, 1…5 V, 0.5…4.5 V (3-wire); DC 0.5…4.5 V ratiometric
Power Supply DC 8…30 V or DC 8…35 V (4…20 mA, 0…5 V, 1…5 V, 0.5…4.5 V); DC 14…30 V or DC 14…35 V (0…10 V); DC 5 V ±10 % (ratiometric)
Wetted Material Stainless steel 316L (< 10 bar); stainless steel 316L and PH grade steel (≥ 10 bar)
Process Connection G⅛B, G¼B, G⅜B, G½B and G¼ female (EN 837); ⅛, ¼ and ½ NPT (ANSI/ASME B1.20.1); M20 × 1.5 (DIN 16288); G¼A, G½A (DIN EN ISO 1179-2); R¼, R⅜, R½ (ISO 7)
Electrical Connection Angular connector DIN EN 175301-803 A or C; circular connector M12 × 1, 4-pin; cable outlet
Ingress Protection IP65 (angular connector) or IP67 (M12 × 1 and cable outlet) per IEC 60529
Medium Temperature 0…+80 °C standard; -40…+100 °C extended range with current output
Service Life 100 million load cycles for measuring ranges > 0.1 bar; 10 million load cycles for ranges ≥ 600 bar or ≤ 0.1 bar