WIKA R-1 Pressure Sensor (Heating & Refrigeration) – 4–20 mA / Switching / Ratiometric, 7–30 VDC, Schrader 7/16-20 UNF, Up To IP69K

WIKA

WIKA R-1 Pressure Transmitter for Heating & Refrigeration

Model R-1

WIKA model R-1 pressure transmitter for heating, refrigeration and air-conditioning plant. Gauge ranges 0…6 to 0…160 bar, 4…20 mA or DC voltage output, all-welded stainless steel measuring cell with no elastomer seal, and a 7/16-20 UNF Schrader option.

Prices on request. Contact us for availability and quotations.

Documents

Need a certificate we have not listed? Ask us and we will send it.

Description

The WIKA model R-1 is a pressure transmitter developed for heating, refrigeration and air-conditioning service. Gauge ranges run from 0…6 bar to 0…160 bar [0…100 to 0…2,400 psi], with vacuum and compound ranges from -1…+7 bar to -1…+45 bar and -0.5…+7 / -0.5…+10 bar. Non-linearity is ≤ ±0.5 % of span (BFSL per IEC 61298-2).

The instrument is built without an elastomer seal: the measuring cell is welded directly to the process connection, and the sensor and process connection are stainless steel throughout, so there is no soft seal in the refrigerant path to permeate or age. The data sheet states the instrument is suitable for flammable refrigerants. Permissible medium temperature is -40…+100 °C, ambient -25…+85 °C, and service life is 10 million load cycles.

Process connections include the 7/16-20 UNF-2B Schrader connection (to 60 bar), a 7/16-20 UNF-2A 90° fitting compatible with SAE J513, G¼B per EN 837, ⅛ and ¼ NPT, R¼ and a stainless steel blowpipe version. Electrical connection is an M12 × 1 circular connector, a Metri-Pack series 150 connector or a cable outlet.

When ordering, state the measuring range, the output signal and matching supply voltage, the process connection, and the electrical connection — the plug connection is IP67 and the cable outlet version is IP69K.

Specifications

Measuring Range (Gauge) 0…6 to 0…160 bar [0…100 to 0…2,400 psi]
Measuring Range (Vacuum / Compound) -1…+7 to -1…+45 bar; also -0.5…+7 and -0.5…+10 bar
Accuracy Non-linearity ≤ ±0.5 % of span (BFSL per IEC 61298-2)
Output Signal 4…20 mA (2-wire); DC 0…10 V and DC 1…5 V (3-wire); DC 0.5…4.5 V ratiometric
Power Supply DC 7…30 V (4…20 mA); DC 8…30 V (1…5 V); DC 14…30 V (0…10 V); DC 4.5…5.5 V (ratiometric)
Process Connection 7/16-20 UNF-2B Schrader (to 60 bar); 7/16-20 UNF-2A 90° compatible with SAE J513; G¼B (EN 837); ⅛ and ¼ NPT; R¼; PT ¼; stainless steel blowpipe
Wetted Material Sensor and process connection stainless steel; measuring cell welded directly to the process connection, no elastomer seal
Electrical Connection Circular connector M12 × 1; Metri-Pack series 150; or cable outlet (0.5 / 1 / 2 / 5 m)
Ingress Protection IP67 (plug connection) or IP69K (cable outlet) per IEC 60529
Medium Temperature -40…+100 °C [-40…+212 °F]
Ambient Temperature -25…+85 °C [-13…+185 °F]
Service Life 10 million load cycles